Characteristics:
The instrument can measure dual pressure (gauge pressure) as well as dual temperature measurement (test clip required, not included) at the same time, with automatic multi-unit pressure conversion and automatic Celsius/Fahrenheit temperature conversion to meet different needs.
Built-in 89 kinds of refrigerant pressure evaporating temperature databases also calculate subcooling superheat to facilitate direct reading of operating process data.
The percentage of vacuum measurement is also tested. Pressure leak measurement, leak time velocity recording.
Get the job done right with this multifunctional, precise and easy-to-use digital distributor.
Safety standards EC / EN61010-1 for design and production.
1) The pressure measured by the Digtal manifold pressure tester is gauge pressure.
2) The pressure test ranges from -101 kPa to 6 MPa (-0.1 bar to 60 bar).
3) The limit pressure is 10 MPa (100 bar).
4) The maximum operating pressure of the standard hose is 600 PSI (approx. 4.13 MPa, 41.3 bar). The limit pressure is 3000 PSI (approx. 20.68 MPa, 206.8 bar).
5) Please confirm the rated pressure value of the tested device before testing. Do not use it if it exceeds the range of the instrument.
6) Do not use or store the instrument in high temperature, high humidity, flammable, explosive and strong electromagnetic fields.
7) Please do not modify the device any internal circuit to avoid damage to the instrument or danger occurs.
8) Please wear qualified protective equipment to protect the user during the test.
9) Use the device in a well-ventilated environment to prevent inhalation of toxic gases.
Specifications:
Pressure test: pressure gauge pressure
Pressure tester: Kpa; MPa; Bar; inHg; PSI.
Pressure test range: 0Kpa - 6000Kpa
Pressure test resolution: 1Kpa
Pressure test accuracy: +/- 0.5% (FS) + 5 dgt
Pressure overload limit: 10000 Kpa (10 MPa; 100 bar;)
Vacuum test: relative vacuum
Vacuum test device: Kpa; MPa; Bar; inHg; PSI.
Vacuum test range: -101Kpa - 0Kpa
Vacuum test resolution: 1 Kpa
Temperature tester: °C (Celsius), °F (Fahrenheit)
Temperature test range: -40°C - 150°C (-40°F - 302°F)
Temperature test resolution:
0.1°C (-40°C - 99.9°C), 1°C (100°C - 150°C)
0.1°F (-40°F - 99.9°F), 1°F (100°F - 302°F)
Temperature test accuracy: +/- 0.5°C + 2dgt +/- 0.9°F + 2dgt
Built-in 89 kinds of refrigerant NIST: According to AmericanNIST standard
Power supplies: 4 x 1.5V (SIZE.AA / LR6) Battery not included
Size: 170*110*50mm/6.7*4.3*2.0in
Package size: 200*150*80mm/7.9*5.9*3.0in
Packaging weight: 950g
Packing list:
1 * Digital Refrigerant Manifold Gauge
1 * User Manual (in English)